9.3 Setup
The prevailing plant conditions inuence the safety of the
measuring system. For this reason, carefully observe the
mounting and installation instructions in the operator's manual.
It is especially important to make sure the mode setting (min./
max.) is correct.
9.4 Reaction during operation and in case of
failure
l The adjustment elements must not be modied during
operation.
l If modi cations have to be made during operation, carefully
observe the safety functions.
l Fault signals that may appear are described in the
appropriate operating instructions manual.
l In case of detected failures or fault signals, the entire
measuring system must be switched out of service and the
process held in a safe condition by means of other
measures.
l An electronics exchange is easily possible and described
in the operating instructions manual.
l If due to the detected failure, the electronics or the
complete sensor is exchanged, the manufacturer must be
informed (incl. a fault description).
9.5 Recurring function test
The recurring function test serves to reveal potential danger-
ous errors that are otherwise not discernible. The function of
the measuring system must be checked at adequate intervals.
The operator is responsible for choosing the type of test and
the intervals in the stated time frame. The time frame depends
on the PFD
avg
value acc. to the chart and diagram in section
"Safety-related characteristics".
In high demand rate, no recurring function test is arranged in
IEC 61508. A proof of the functional eciency is seen in the
more frequent demand of the measuring system. In double
channel architectures it is useful to proof the redundancy by
recurring function tests in appropriate intervals.
The test must be carried out in a way that veries the awless
operation of the safety functions in conjunction with all system
components.
Mounting and install ation
Functional safety
30 OPTISWITCH 310 0 C - with two-wire output
29955-EN-060112