6.2 Adjustment elements
5
1
2
3
4
Fig. 11: Oscillator VB 60Z - Two-wire output
1 Potentiometer for switching point adaptation
2 DIL switch for mode adjustment
3 Ground terminal
4 Terminals
5 Control lamp
With the potentiometer you can adapt the switching point to the
solid. It is already factory-preset and must be adjusted only in
special cases.
By default, the potentiometer of OPTISWITCH 3100 C is set to
mid position (>0.02 g/cm³ or >0.0008 lbs/in³). In case of very
light-weight solids, you have to turn the potentiometer to the
complete left position (>0.008 g/cm³ or >0.0003 lbs/in³).
Hence the OPTISWITCH 3100 C will be more sensitive and
can detect light-weight solids more reliably.
For instruments detecting solids in water, these values are not
applicable. The potentiometer is preset and must not be
changed.
With the mode adjustment (min./max.) you can determine the
output current.
When using a signal conditioning instrument , always set the
mode switch to max .
mode.
In this case you select the requested mode acc. to the
"Function chart" (max.-max. detection or overll protection,
Switching point adaptation (1)
Mode adjustment (2)
OPTISWITCH 3100 C - with two-wire output 19