16 VAC D300 PSS EVE0105 A-(en)
A
B
C
1 2
1 9
"
#
#
Built-in Limit Switch
(Options for electronics family AI 638 per EC- Certificate of
conformity PTB 00 ATEX 2128)
Inductive Limit Switch
standard version (SJ2-N) .......Option STD
security version (SJ2-SN) ......Option SEC
Microswitches...............Option MIC*
Stroke / angle derived from positioner feedback,
two-wire system
Output.................2inductive proximity sen-
sors acc. to DIN 19 234 or NAMUR for connection to
switching amplifier
1)
Current consumption
vane clear ............>2.2mA
vaneinterposed........<1mA
for control circuit with the following electrical values:
supply voltage .........DC8V,R
i
approx. 1 kOhm
supply voltage range....DC5...25 V (only with ZZZ)
residual ripple ..........<10%p.p.
permissible
line resistance .........<100Ohms
Response characteristic
2) 3)
switching differential .....<1%
switching point repeatability .....<0.2%
Terminals for GW1........41+,42
GW2........51+,52
Electrical classification:
Version STD" and SEC“:
(Electronics family AI 638 per EC- Certificate of conformity
PTB 00 ATEX 2128)
see Certificate of Conformity EX EVE0105 A
TypeAI638K...........II2GEExiaIICT6
Types of protection and temperature classes as basic device.
For use in hazardous areas in circuits certified as intrinsic-
ally safe with the following maximum values:
Ui= 16 V, Ii= 25 mA, Pi= 64 mW
Internal capacitance and inductance: Ci= 30 nF, Li= 100 µH
The electric circuits of "Built-in Limit Switch" are galvanically
separated from all other circuits and from ground.
Type of protection FM “intrinsic safety”
Class I, Div. 1, Groups A, B, C, D;
hazardous locations indoor and outdoor, NEMA Type 4X *)
Type of protection FM “non-incendive”
Class I, Div. 2, Groups A, B, C, D, F, G;
hazardous locations indoor and outdoor, NEMA Type 4X
Type of protection CSA “intrinsic safety”
Class I, Div. 1, Groups A, B, C, D;
hazardous locations indoor and outdoor, NEMA Type 4X *)
*) Under development
1) Operating mode min. (= low) / max. (= high)
selectable by adjustment of switch vanes
2) Data measured according to VDI/VDE 2177
3) With stroke 30 mm and lever length 90 mm
Built-in Limit Switch
Built-in Pressure sensors, Code Option SD *)
For supply air and output y1 to actuator
Measuring range .........0to8bar(0to120psig)
Accuracy ...............0.5%
Temperature influence .....0.5%/10k(40to80°C)(-40 to 176ºF)
Pressure sensors 50